Fixed Speed Rotary Compressors
Inverter-driven system promotes maximum compressor efficiency. The system detects subtle temperature changes and automatically adjust its capacity output. These lead to stabilizing temperature, minimizing power consumption and optimizing humidity control.
Models | Capacity | Input | Norminal Output | COP | EER | Run Cap | Weight | Oil | ||||
W | Kcl/hr | Btu/hr | Watt | Amps | HP | kW | W/W | Btu/hr* w | mF/VAC | kgs | cc | |
RE189VHSMT | 3210 | 2760 | 10953 | 1010 | 4.80 | 1.1 | 0.85 | 3.18 | 10.84 | 30/370 | 15.1 | 520 |
Model | RE Series | PE Series | NE Series |
---|---|---|---|
Compressor | |||
Type | Rolling piston type rotary | ||
Displacement (mc3/rev) | 13.5-31.3 | 28.1-41.7 | 28.0-56.9 |
Refrigerant type | R-407C | ||
Pressure | |||
Maximum Condensing | 1.10 MPaG ~2.83 MPaG (159.5 psiG - 410.4 psiG) | ||
Evaporating | 0.26 MPaG ~0.73 MPaG (37.7 psiG - 105.9 psiG) | ||
Compression Ratio | 6 or less | 8 or less | |
Abnormal rise in pressure | 4.9 MPaG (710.6psiG) or less | ||
Temprature | |||
Condensing | 28°C ~ 65°C | ||
Evaporating | -10°C ~ 15°C | ||
Discharged gas max | 120°C (248°F) In case of heat pump or de-humidipier, this limit is 110°C (230°F) |
||
Suction gas max | must be over 0°C (No liquid back) | ||
Discharged gas superheat | 20°C or more | ||
Outdoor ambient temp | Air cond : 20°C~43°C (68°F~109.4°F) Heat pump: -10°C~43°C(14°F~109.4F) |
||
Electrical | |||
Supply voltage (during operation) | Rated voltage + or - 10% | ||
Starting voltage | Maximum 80% of rated voltage (at 1.01 MPa balancing pressure in case of 208-230 v Rated voltage (N code compressor) the starting voltage shall be 85% or more . This shall be measured at compressor terminal at instance of start.) |
||
Reverse phase (rotation) | Compressor is not designed to run reverse phase | ||
Frequency range | Rated frequency + or - 2% | ||
ON/OFF | |||
ON/OFF Frequency | Less than 170000 cycles | ||
ON/OFF Cycle | The ON/OFF cycle shall be amximum of 10 times/hr OFF time shall be the time until the high side and low side pressure reach to balance pressure (more than 3 minuts) |
||
Pipe Stress | 3.5Kg/mm2 or less at start and stom conditions (1.8 kg/mm2 during operation) |
||
Refrigerant Circuit | |||
Piping Vibration | Maximum 0.8mm | ||
Inclination of compressor | Within 5° |